NRGence eco PDUs offer remote power control combined with real-time power measurement - allowing you to control and monitor the power status of devices attached to the PDUs, either at the PDU device or bank level, from practically any location via a TCP/IP connection **.
The eco PDU also offers comprehensive power analysis reports providing precise measurements of current, voltage, power and watt-hour in a real-time display.
Installation and operation are both fast and easy: plugging cables into their appropriate ports and user-friendly browser-based configuration and management is all that is entailed. Since the eco PDU firmware is upgradeable over the Net, you can stay current with the latest functionality improvements simply by downloading updates from our website as they become available.
NRGence eco PDUs support any 3rd party V1, V2, V3 SNMP Manager Software and NRGence eco Sensors (eco PDU Manager Software). Eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it.
Note:
* Sensors are optional accessories. A sensor-enabled installation is required to generate more complete energy efficient data and chart. Higher sensor installation density is helpful to generate more accurate data.
**eco PDUs are primarily designed for access via Intranet; extra network security protection is suggested for Internet
access usage.
Diagram

Specifications
eco PDU
Function |
PE5340sB |
PE5340sG |
Electrical |
Nominal Input Voltage |
100 – 240 VAC |
100 – 240 VAC |
Maximum Input Current |
30A Max; 24A(UL de-rated) |
32A Max |
Input Frequency |
50-60 Hz |
50-60 Hz |
Input Connection |
NEMA L6-30P |
IEC 60309 32A |
Input Power |
6240 VA(Max); 4992 VA(UL de-rated) |
7360 VA(Max) |
Outlet Type |
Total : 40 x IEC320 C13 Bank1 : Outlet 1 – 20 ; 20 x C13 Bank2 : Outlet 21 – 40 ; 20 x C13 |
Total : 40 x IEC320 C13 Bank1 : Outlet 1 – 20 ; 20 x C13 Bank2 : Outlet 21 – 40 ; 20 x C13 |
Nominal Output Voltage |
100 – 240 VAC |
100 – 240 VAC |
Maximum Output Current (Outlet) |
C13: 10A(Max); 12A(UL de-rated) |
C13: 10A (Max) |
Maximum Output Current (Bank) |
15A(Max); 12A(UL de-rated) |
16A(Max); TUV De-rated 15A(Max) |
Maximum Output Current (Total) |
30A(Max); 24A(UL de-rated) |
32A(Max); TUV De-rated 30A(Max) |
Breakers |
2 x 16A UL489 breaker |
1 x 16A UL489 breaker |
Metering |
Outlet Level Current, Voltage, VA, PF, KWh Monitoring |
Outlet Level Current, Voltage, VA, PF, KWh Monitoring |
Outlet Switching |
None |
None |
Environment Sensor Ports |
2 |
2 |
Metering Accuracy |
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Physical Properties |
Dimensions (L x W x H) |
135.98 x 6.60 x 4.40 cm (53.54 x 2.6 x 1.73 in.) |
135.98 x 6.60 x 4.40 cm (53.54 x 2.6 x 1.73 in.) |
Weight |
4.83 kg ( 10.64 lb ) |
4.83 kg ( 10.64 lb ) |
Power Cord Length |
1.6m |
1.6 m |
Environmental |
Temperature (Operating / Storage) |
0–50°C / -20–60°C |
0–40°C / -20–60°C |
Humidity (Operating & Storage) |
0–80% RH, Non-Condensing |
0–80% RH, Non-Condensing |
Compliance |
EMC Verification |
FCC Part 15 Class A, Others by Request |
CE, Others by Request |
Safety Verification |
By Request |
CE-LVD, Others by Request |