As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data centre power usage.

The NRGence PE5340s is an intelligent PDUs that contains 40 AC outlets and is available in IEC or NEMA input configurations. The PE5340s provides secure, centralised, intelligent, power management of data centre IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the centre's health environment via sensors *.

NRGence eco PDUs offer remote power control combined with real-time power measurement - allowing you to control and monitor the power status of devices attached to the PDUs, either at the PDU device or bank level, from practically any location via a TCP/IP connection **.

The eco PDU also offers comprehensive power analysis reports providing precise measurements of current, voltage, power and watt-hour in a real-time display.

Installation and operation are both fast and easy: plugging cables into their appropriate ports and user-friendly browser-based configuration and management is all that is entailed. Since the eco PDU firmware is upgradeable over the Net, you can stay current with the latest functionality improvements simply by downloading updates from our website as they become available.

NRGence eco PDUs support any 3rd party V1, V2, V3 SNMP Manager Software and NRGence eco Sensors (eco PDU Manager Software). Eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it.

Note:
* Sensors are optional accessories. A sensor-enabled installation is required to generate more complete energy efficient data and chart. Higher sensor installation density is helpful to generate more accurate data.
**eco PDUs are primarily designed for access via Intranet; extra network security protection is suggested for Internet
access usage.

Diagram

ATEN Metered PDU PE5340s on Clearance Sale

Specifications

eco PDU

 

Function PE5340sB PE5340sG
Electrical
Nominal Input Voltage 100 – 240 VAC 100 – 240 VAC
Maximum Input Current 30A Max; 24A(UL de-rated) 32A Max
Input Frequency 50-60 Hz 50-60 Hz
Input Connection NEMA L6-30P IEC 60309 32A
Input Power 6240 VA(Max); 4992 VA(UL de-rated) 7360 VA(Max)
Outlet Type Total : 40 x IEC320 C13
Bank1 : Outlet 1 – 20 ; 20 x C13
Bank2 : Outlet 21 – 40 ; 20 x C13
Total : 40 x IEC320 C13
Bank1 : Outlet 1 – 20 ; 20 x C13
Bank2 : Outlet 21 – 40 ; 20 x C13
Nominal Output Voltage 100 – 240 VAC 100 – 240 VAC
Maximum Output Current (Outlet) C13: 10A(Max); 12A(UL de-rated) C13: 10A (Max)
Maximum Output Current (Bank) 15A(Max); 12A(UL de-rated) 16A(Max); TUV De-rated 15A(Max)
Maximum Output Current (Total) 30A(Max); 24A(UL de-rated) 32A(Max); TUV De-rated 30A(Max)
Breakers 2 x 16A UL489 breaker 1 x 16A UL489 breaker
Metering Outlet Level Current, Voltage, VA, PF, KWh Monitoring Outlet Level Current, Voltage, VA, PF, KWh Monitoring
Outlet Switching None None
Environment Sensor Ports 2 2
Metering Accuracy Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Physical Properties
Dimensions (L x W x H) 135.98 x 6.60 x 4.40 cm
(53.54 x 2.6 x 1.73 in.)
135.98 x 6.60 x 4.40 cm
(53.54 x 2.6 x 1.73 in.)
Weight 4.83 kg ( 10.64 lb ) 4.83 kg ( 10.64 lb )
Power Cord Length 1.6m 1.6 m
Environmental
Temperature (Operating / Storage) 0–50°C / -20–60°C 0–40°C / -20–60°C
Humidity (Operating & Storage) 0–80% RH, Non-Condensing 0–80% RH, Non-Condensing
Compliance
EMC Verification FCC Part 15 Class A, Others by Request CE, Others by Request
Safety Verification By Request CE-LVD, Others by Request
£368.51