As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data centre power usage. The NRGence PE5220s eco PDU is an intelligent PDU that contains 20 AC outlets and is available in various IEC or NEMA socket configurations. It provides the ability to monitor the centre's health environment via sensors*.

NRGence eco PDU offers real-time power measurement - allowing you to monitor the power status of devices attached to the PDUs, either at the PDU device or Bank level, from practically any location via a TCP/IP connection.

It also offers comprehensive power analysis reports – providing precise measurements of current, voltage, power and watt-hour in a real-time display.

NRGence eco PDU supports any 3rd party v1, v2 & v3 SNMP Manager Software and ATEN eco Sensors (eco PDU Manager Software). eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it.

With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable, and most cost-effective way to remotely monitor power status for multiple computer installations and allocate power resources in the most efficient way possible.

* Note:
1. Sensors are optional accessories. A sensor-enabled installation is required to generate a complete energy efficient data and chart. Higher sensor installation density is helpful to generate more accurate data.
2. eco PDUs are primarily designed for access via Intranet; extra network security protection is suggested for Internet access usage.

Diagram

ATEN metered-pdu pe5220s on Clearance Sale

Specifications

eco PDU

 

Function PE5220sA PE5220sB PE5220sG
Electrical
Nominal Input Voltage 100 – 120 VAC 100 – 240 VAC 100 – 240 VAC
Maximum Input Current 20A Max; 16A(UL de-rated) 20A Max; 16A(UL de-rated) 16A Max
Input Frequency 50-60 Hz 50-60 Hz 50-60 Hz
Input Connection NEMA 5-20P NEMA 6-20P IEC 60320 C20
Input Power 2400 VA(Max); 1920 VA(UL de-rated) 4160 VA(Max); 3328 VA(UL de-rated) 3680 VA(Max)
Outlet Type Total: 20 x NEMA 5-15R Total: 20 x IEC320 C13 Total: 20 x IEC320 C13
Nominal Output Voltage 100 – 120 VAC 100 – 240 VAC 100 – 240 VAC
Maximum Output Current (Outlet) NEMA 5-15R: 15A(Max); 12A(UL de-rated) C13: 15A(Max); 12A(UL de-rated) C13: 10A(Max)
Maximum Output Current (Bank) 20A(Max); 16A(UL de-rated) 20A(Max); 16A(UL de-rated) 16A(Max)
Maximum Output Current (Total) 20A(Max); 16A(UL de-rated) 20A(Max); 16A(UL de-rated) 16A(Max)
Breakers 1 x 20A Non-Fuse breaker 1 x 20A Non-Fuse breaker 1 x 16A Non-Fuse breaker
Metering Bank level Current, Voltage, VA , PF and KWh Monitoring Bank level Current, Voltage, VA , PF and KWh Monitoring Bank level Current, Voltage, VA , PF and KWh Monitoring
Outlet Switching None None None
Environment Sensor Ports 2 2 2
Metering Accuracy Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Physical Properties
Dimensions (L x W x H) 69.14 x 6.60 x 4.40 cm
(27.22 x 2.6 x 1.73 in.)
69.14 x 6.60 x 4.40 cm
(27.22 x 2.6 x 1.73 in.)
69.14 x 6.60 x 4.40 cm
(27.22 x 2.6 x 1.73 in.)
Weight 2.13 kg ( 4.69 lb ) 2.13 kg ( 4.69 lb ) 2.13 kg ( 4.69 lb )
Power Cord Length 3 m 3 m 3 m
Environmental
Operating Temperature 0–50°C 0–50°C 0–50°C UL 60950(EN 60950 de-rated 0°C–30°C)
Storage Temperature -20–60°C -20–60°C -20–60°C
Humidity (Operating & Storage) 0 – 80% RH, Non-Condensing 0 – 80% RH, Non-Condensing 0 – 80% RH, Non-Condensing
Compliance
EMC Verification FCC Part 15 Class A, Others by Request FCC Part 15 Class A, Others by Request CE, Others by Request
Safety Verification TUV-CB, Others by Request TUV-CB, Others by Request TUV-CB, CE-LVD, Others by Request
£266.51